Title 7 PUBLIC SERVICES AND UTILITIES
Chapter 7.68 WATER DIVISION
7.68.070 Cross connection control.
A. Cross-Connections. No water service shall be installed or
continued in use by the purveyor unless the water supply is protected by
backflow prevention devices as may be required by this section. The installation
or maintenance of a cross-connection which will endanger the water quality of
the potable water supply of the city of Yakima shall be unlawful and is
prohibited. Any such cross-connection now existing or hereafter installed is
declared to be a public nuisance and the same shall be abated. The control or
elimination of cross-connections shall be in accordance with this section,
together with the latest addition of appropriate manuals of standard practice
pertaining to cross-connection control approved by the secretary. The manager
shall have the authority to establish requirements more stringent than state
regulations if he deems that the conditions so dictate. The purveyor shall adopt
rules and regulations as necessary to carry out the provisions of this
section.
B. Use of Backflow Prevention Devices.
(1) Backflow prevention devices shall be installed at the
time on the premises or the materials used in connection with service connection
or within any premises where, in the judgment of the purveyor, the nature and
extent of the activities, or the materials stored on the premises, would present
an immediate and dangerous hazard to health and/or be deleterious to the quality
of water should a cross-connection occur; even though such cross-connection does
not exist at the time the backflow prevention devices shall be installed under
circumstances including but not limited to the following:
(a) Premises having an auxiliary water supply, unless the
quality of the auxiliary supply is acceptable to the purveyor.
(b) Premises having internal cross-connections that are not
correctable, or intricate plumbing arrangements which make it impracticable to
ascertain whether or not cross-connections exist.
(c) Premises where entry is restricted so that inspections
for cross-connections cannot be made with sufficient frequency or at
sufficiently short notice to assure that cross-connections do not
exist.
(d) Premises having a repeated history of cross-connections
being established or re-established.
(e) Premises on which any substance is handled under pressure
so as to permit entry into the public water supply, or where a cross-connection
could reasonably be expected to occur. This shall include the handling of
process waters and cooling waters.
(f) Premises where materials of toxic or hazardous nature are
handled in such a way that if back siphonage should occur, a serious health
hazard might result.
(g) The following types of facilities will fall into one of
the above categories where a backflow prevention device is required to protect
the public water supply. A backflow prevention device shall be installed at
these facilities unless the purveyor and secretary determine that no hazard
exists.
1. Hospitals, mortuaries, clinics;
2. Laboratories;
3. Metal plating industries;
4. Piers and docks;
5. Sewage treatment plants;
6. Food or beverage processing plants;
7. Chemical plants using a water process;
8. Petroleum processing or storage plants;
9. Radioactive material processing plants or nuclear
reactors;
10. Others specified by the secretary.
(h) Other premises, as specified by the manager, where
backflow prevention devices are required to protect the public water
supply.
(2) The type of protective device required shall depend on
the degree of hazard which exists;
(a) An air-gap separation or a reduce pressure principle
backflow prevention device shall be installed where the public water supply may
be contaminated with sewage, industrial waste of a toxic nature, or other
contaminant which could cause a health or system hazard.
(b) In the case of a substance which may be objectionable but
not hazardous to health, a double check valve assembly, air-gap separation, or a
reduced pressure principle backflow prevention device shall be
installed.
(3) Backflow prevention devices required by this section
shall be installed at the meter, or at a location designated by the purveyor.
The device shall be located so as to be readily accessible for maintenance and
testing, and furthermore, where no part of the device will be
submerged.
(4) Backflow prevention devices required by this section
shall be installed under the supervision of, and with the approval of, the
purveyor.
(5) The policies, procedures, and criteria for determining
appropriate levels of protection shall be in accordance with the "Accepted
Procedure and Practice in Cross Connection Control Manual--Pacific Northwest
Section--American Waterworks Association, Third Edition," or any superseding
edition.
(6) Any protective device required by this section shall be a
model approved by the manager. A double check valve assembly or a reduced
pressure principle backflow prevention device will be approved if it has
successfully passed performance tests of the University of Southern California
Engineering Center or other testing laboratories satisfactory to the secretary
and the manager. These devices shall be furnished and installed by and at the
expense of the customer.
(7) Backflow prevention devices installed pursuant to this
section, except atmospheric vacuum breakers, shall be inspected and tested
annually, or more often if necessary. Maintenance shall be at the
customer’s expense. Whenever the devices are found to be defective, they
shall be repaired, overhauled, or replaced at the customer’s expense.
Inspections, tests, repairs, and records thereof shall be accomplished under the
purveyor’s supervision by certified testers and the customer will be
charged according to the following schedule of fees:
|
(a) For air gap separation inspection
|
$ 15.00
|
|
(b) For pressure atmospheric vacuum breaker test
|
15.00
|
|
(c) For double check valve assembly test
|
25.00
|
|
(d) For reduced pressure backflow device test
|
25.00
|
(8) No underground sprinkling device will be installed
without adequate backflow prevention devices at the point from which the water
for irrigation is taken from the public water supply.
(9) Failure of the customer to cooperate in the installation,
maintenance, testing or inspection of backflow prevention devices required by
this section and Washington Administrative Code 248-54 shall be grounds for the
termination of water service to the premises, or, in the alternative, the
installation of an air-gap separation at the customer’s expense.
C. Cross-Connection Inspection.
(1) No water shall be delivered to any structure hereafter
built within the city of Yakima or within areas served by the city water until
the same shall have been inspected by the purveyor for possible
cross-connections and been approved as being free of same.
(2) Any construction for industrial or other purposes which
is classified as hazardous facilities pursuant to subsection B(1)(g), where it
is reasonable to anticipate intermittent cross-connections, or as determined by
the manager, shall be protected by the installation of one or more backflow
prevention devices at the point of service from the public water supply or any
other location designated by the purveyor.
(3) Inspections shall be made periodically of all buildings,
structures, or improvements of any nature now receiving water through the
city’s system, for the purpose of ascertaining whether cross-connections
exist. Such inspections shall be made by the purveyor.
D. Installation Permits. If cross-connection control devices
are found to be necessary, the owner of the property served must apply to the
city of Yakima code administrator for an installation permit.
E. Additional Remedies. In the event an improper
cross-connection is not corrected within the time limit set by the manager, or,
in the event the purveyor is refused access to any property for the purpose of
determining whether or not cross-connections exist; delivery of water to the
property shall cease until the deficiency is corrected to the purveyor’s
satisfaction. In addition, the purveyor may effect the necessary repairs or
modifications at the expense of the property owner and refuse delivery of water
to the property until the cost thereof shall have been paid. (Ord. 97-16 §
8, 1997: Ord. 3078 § 2, 1988).